Logo image
SWRO feed water quality improvement using subsurface intakes in Oman, Spain, Turks and Caicos Islands, and Saudi Arabia
Journal article   Peer reviewed

SWRO feed water quality improvement using subsurface intakes in Oman, Spain, Turks and Caicos Islands, and Saudi Arabia

Rinaldi M. Rachman, Sheng Li and Thomas M. Missimer
Desalination, Vol.351, pp.88-100
10-15-2014

Abstract

Engineering Engineering, Chemical Physical Sciences Science & Technology Technology Water Resources
Water quality sampling and analysis conducted at four global locations, along the shorelines of the Arabian Sea, the Red Sea, the Mediterranean Sea, and the Caribbean Sea, demonstrated that subsurface intakes (wells) provide a robust degree of feed water treatment close to that provided by energy-intensive, conventional pretreatment systems. SDI values were reduced in virtually all cases to below 3. In vertical wells, from 70 to 100% of the TEP and 50% of the TOC and DOC found in natural seawater were removed in the aquifer. Reduction in the concentration of the organic fractions was selective based on molecular weight with the biopolymers nearly fully removed. Humic substances, building blocks, and light organic substances were removed at lesser percentages. Site geology was not the predominant factor affecting the removal efficiency, but the length of the flow path from the sea to the wells and the hydraulic retention time appear to be most significant. A comparison between vertical wells, a tunnel intake system, and a horizontal drain system at Alicante, Spain, demonstrated that the vertical wells performed best followed by the tunnel system, and the horizontal drain system which showed a breakthrough of algae and a very high organic carbon concentration. (C) 2014 Elsevier B.V. All rights reserved.

Metrics

23 Record Views
58 Times Cited - Scopus

Details

UN Sustainable Development Goals (SDGs)

This output has contributed to the advancement of the following goals:

#6 Clean Water and Sanitation
Logo image